Cummins — Cummins CFP83 Series Fire Pump Drive Engines Operation & Maintenance Manual

Page 5 - 30 Section 5 – Maintenance Procedures CFP83 Series Fill CAUTION The system must be filled properly to prevent air locks. During filling, air must be vented from the engine coolant passages. The system has a design fill rate of 10 liters/minute [2.8 gal/min]. CAUTION Never use water alone for coolant. Damage from corrosion can be the result of using water alone for coolant. Use a mixture of 50-percent water and 50-percent ethylene glycol antifreeze to fill the cooling system. Coolant Capacity (Engine Only): 4.50 liters [1.19 US Gal] Drawing No. 9777, Section 5, Rev. 02-07 Operate the engine for 5 minutes with the coolant temperature above 82°C [180°F]. Shut the engine off.

Drain the cooling system. NOTE: If the water being drained is still dirty, the system must be flushed again until the water is clean.