Cummins — Cummins CFP83 Series Fire Pump Drive Engines Operation & Maintenance Manual

Page 5 - 40 Section 5 – Maintenance Procedures CFP83 Series Use the Cummins belt tensioner gauge, Part No. 3822524, to measure the tension in the drive belt. This needs to be in the range of 360 to 490 N•m [266 to 361 ft-lb]. Check the tensioner arm, pulley, and stops for cracks. If any cracks are noticed, the tensioner must be replaced. With the belt on, verify that neither tensioner arm stops are in contact with the spring casing stop. If either stop is touching, the drive belt must be replaced. After replacing the belt, if the tensioner arm stops are still in contact with the spring casing stop, replace the tensioner. Remove the drive belt, and check the torque of the tensioner capscrew.

After checking the torque, use a breaker bar with a 3/8-inch ratchet to rotate the tensioner slowly away from the area of belt contact. If the arm rotates with any roughness or hesitancy, replace the tensioner. Torque Value: 43 N•m [32 ft-lb] Drawing No. 9777, Section 5, Rev. 02-07