Cummins — Cummins CFP83 Series Fire Pump Drive Engines Operation & Maintenance Manual

Section 7 – Adjustment, Repair, and Replacement Page 7-9 CFP83 Series Belt Guard Removal/Installation (Cont) Remove Drain the coolant from the coolant heat exchanger. Refer to Drain and Flush Cooling System in Section 5. Remove the Coolant Heat Exchanger’s Coolant Outlet Hose and Vent Hose. Refer to Coolant Hose Removal / Installation in this section. Remove the three bolts and the belt guard. Install NOTE : Install only Cummins approved replacement belt guard (Cummins Fire Power Part No. 9625 [CFP83- F10, F20, F30] or Part No. 9627 [CFP83- F40]). When other work is completed, install the belt guard using the three bolts. Torque as per Capscrew Markings and Torque Values in Section 10.

Install the Coolant Heat Exchanger’s Coolant Outlet Hose and Vent Hose. Refer to Coolant Hose Removal / Installation in this section. Refill the coolant. Refer to Drain and Flush Cooling System in Section 5. Follow-Up Install the Upper Engine Coolant Hose at the heat exchanger. Install the Lower Engine Coolant and Fill Hose at the heat exchanger. Install the Coolant Vent Hose at the heat exchanger. Drawing No. 9777, Section 7, Rev. 02-07