Cummins — Cummins CFP83 Series Fire Pump Drive Engines Operation & Maintenance Manual

Section 7 – Adjustment, Repair, and Replacement Page 7-11 CFP83 Series Belt Guard Removal/Installation (Cont) NOTE : Start the engine and do a quick check for leaks. If any coolant leaks are observed, stop the engine, repair the leak, check coolant level, then restart the engine. Start the engine. Refer to Normal Local Starting Procedure in Section 3. Check for and repair any coolant leaks. Ensure that repairs are completed satisfactorily. Stop the engine. Place the AUTO/MANUAL rocker switch in the AUTO position. Return the fire protection system to operating status. Drawing No. 9777, Section 7, Rev. 02-07