Cummins — Cummins CFP83 Series Fire Pump Drive Engines Operation & Maintenance Manual

Section 7 – Adjustment, Repair, and Replacement Page 7-19 CFP83 Series Coolant Heat Exchanger Removal/Installation (Cont) Remove Provide temporary support for the coolant heat exchanger in order to avoid dropping it. Remove the four back sets of nuts, washers, and bolts at the heat exchanger mounting clamps. Remove the heat exchanger and clamps from the engine. Disassemble If required for replacement, remove the two front sets of nuts and bolts at the coolant heat exchanger clamps. If required for replacement, remove the zinc plug and other pipe fittings from the heat exchanger. Assemble NOTE : Use teflon or other pipe sealant when installing threaded pipe fittings.

If missing, install the zinc plug (Cummins Fire Power Part No. 9750) and brass fitting (Cummins Fire Power Part No. 9751) in the bottom of the heat exchanger. Torque Values: As per capscrew markings and torque values in Section 10 If missing, install the pipe fittings removed from the original heat exchanger. Refer to Drawing 8919 in Section 13 for component information. If removed, position the two clamps on the heat exchanger and install the two front sets of nuts and bolts at the coolant heat exchanger clamps. Do not tighten at this time. Refer to Drawing 8919 in Section 13 for component information. Drawing No. 9777, Section 7, Rev. 02-07