Cummins — Cummins CFP83 Series Fire Pump Drive Engines Operation & Maintenance Manual

Page 7-38 Section 7 – Adjustment, Repair, and Replacement CFP83 Series Raw Water Pressure Regulator Removal/Installation NOTE : This section applies only to pressure regulators supplied by Cummins Fire Power. These procedures should be modified for alternative piping or components as supplied by the customer. NOTE : This section applies to both the normal and bypass lines. Prepare (Bypass Line) Place the AUTO/MANUAL Switch at the local panel in the MANUAL position. Close the Raw Water Manifold Bypass Line Inlet Isolation Valve. Close the Raw Water Manifold Bypass Line Outlet Isolation Valve. Prepare (Normal Line) Place the AUTO/MANUAL Switch at the local panel in the MANUAL position.

Close the Raw Water Manifold Normal Line Inlet Isolation Valve Close the Raw Water Manifold Normal Line Outlet Isolation Valve. Drawing No. 9777, Section 7, Rev. 02-07