Cummins — Cummins CFP83 Series Fire Pump Drive Engines Operation & Maintenance Manual

Section 7 – Adjustment, Repair, and Replacement Page 7-39 CFP83 Series Raw Water Pressure Regulator Removal/Installation (Cont) Remove (Bypass Line) Loosen the pipe union upstream of the pressure regulator. Unscrew the pressure regulator from the outlet isolation valve. As required, remove the pipe nipples from the pressure regulator. Remove (Normal Line) Loosen the pipe union downstream of the pressure regulator. Unscrew the pressure regulator from the solenoid valve. As required, remove the pipe nipples from the pressure regulator. Install (Bypass Line) When the pressure regulator is repaired or replaced, prepare it for installation. NOTE :

Use pipe dope or silicon sealant on threaded fittings. As required, install the pipe nipples on the pressure regulator. Tighten with a pipe wrench or equivalent. Screw the pressure regulator onto the outlet isolation valve. Align and connect the pipe union. Tighten with a pipe wrench or equivalent. Drawing No. 9777, Section 7, Rev. 02-07