Cummins — Cummins CFP83 Series Fire Pump Drive Engines Operation & Maintenance Manual

Page 7-40 Section 7 – Adjustment, Repair, and Replacement CFP83 Series Raw Water Pressure Regulator Removal/Installation (Cont) Install (Normal Line) When the pressure regulator is repaired or replaced, prepare it for installation. NOTE : Use pipe dope or silicon sealant on threaded fittings. As required, install the pipe nipples on the pressure regulator. Tighten with a pipe wrench or equivalent. Screw the pressure regulator onto the solenoid valve. Align and connect the pipe union. Tighten with a pipe wrench or equivalent. Follow-Up (Bypass Line) Check the pressure regulator setpoint.

(Refer to instructions in Section 3.) If required, open the Raw Water Manifold Bypass Line Inlet Isolation Valve. If required, open the Raw Water Manifold Bypass Line Outlet Isolation Valve. Verify that raw water flow is established through the heat exchanger. When flow is verified, close the bypass line outlet valve. Ensure that the normal line inlet and outlet valves are both open. Ensure that the pressure gauge isolation valve is open. Ensure that repairs are completed satisfactorily. Place the AUTO/MANUAL Switch at the local panel in the AUTO position. Drawing No. 9777, Section 7, Rev. 02-07