Section 7 – Adjustment, Repair, and Replacement Page 7-41 CFP83 Series Raw Water Pressure Regulator Removal/Installation (Cont) Follow-Up (Normal Line) Check the pressure regulator setpoint. (Refer to instructions in Section 3.) If required, open the Raw Water Manifold Normal Line Inlet Isolation Valve. If required, open the Raw Water Manifold Normal Line Outlet Isolation Valve. As required, close the bypass line outlet valve. Ensure that the pressure gauge isolation valve is open. Start the engine to operate the raw water solenoid valve. (Refer to instructions in Section 3.) Verify that raw water flow is established through the heat exchanger. When flow is verified, stop the engine.
Observe that raw water flow stops. Ensure that repairs are completed satisfactorily. Place the AUTO/MANUAL Switch at the local panel in the AUTO position. Drawing No. 9777, Section 7, Rev. 02-07