Page 7-42 Section 7 – Adjustment, Repair, and Replacement CFP83 Series Raw Water Solenoid Valve Removal/Installation NOTE : This section applies to solenoid valves supplied by Cummins Fire Power. Prepare Place the AUTO/MANUAL Switch at the local panel in the MANUAL position. WARNING Batteries can emit explosive gases. To reduce the possibility of personal injury, always ventilate the compartment before servicing the batteries. To reduce the possibility of arcing, remove the negative (-) battery cable first and attach the negative (-) battery cable last. Disconnect the positive battery cables from both batteries. Disconnect any customer supplied battery chargers.

Close the Raw Water Manifold Normal Line Inlet Isolation Valve. Close the Raw Water Manifold Normal Line Outlet Isolation Valve. Remove NOTE: Minimize the loss of wire when cutting the splices. NOTE: Tag each end of the wire before making the cut. Cut the butt-splices at the connection between the two solenoid valve pigtail wires and the fire pump electrical harness. Loosen the union fitting between the solenoid valve and the pressure regulator. Unscrew the solenoid valve from the outlet isolation valve or inlet nipple. Remove the solenoid valve. If appropriate for replacement, remove the pipe fittings from the solenoid valve. Drawing No. 9777, Section 7, Rev. 02-07