Cummins — Cummins CFP83 Series Fire Pump Drive Engines Operation & Maintenance Manual

Section 7 – Adjustment, Repair, and Replacement Page 7-43 CFP83 Series Raw Water Solenoid Valve Removal/Installation (Cont) Install NOTE : Install only Cummins approved replacement solenoid valves [Cummins Fire Power Part No. 8210G4-12VDC (12 VDC) or 8210G4-24VDC (24 VDC)]. NOTE : Use thread sealant when making threaded plumbing connections. If removed, install the inlet and outlet fittings on the solenoid valve. Position the solenoid valve and start threading it into the outlet valve or onto the outlet valve nipple. Thread the valve until it is tight and so that the electrical housing is facing up. Align and tighten the union connection. NOTE :

Use termination techniques that meet all local requirements. Cummins recommends crimped and insulated butt splices. NOTE : The solenoid valve’s green pigtail lead is not used. The other two leads are not polarity dependent. Splice the two solenoid pigtail leads to the fire pump harness solenoid leads. Drawing No. 9777, Section 7, Rev. 02-07