Page 7-66 Section 7 – Adjustment, Repair, and Replacement CFP83 Series Coolant Filter Assembly Removal/Installation (Cont) Follow-Up Install the coolant system pressure cap (Cummins Fire Power Part No. 11407). Start the engine. Refer to Normal Local Starting Procedure in Section 3. Check for and repair any coolant leaks. After the air has been purged from the system, stop the engine. WARNING Do not remove the pressure cap from a hot engine. Wait until the coolant temperature is below 50°C [120°F] before removing the pressure cap (Cummins Fire Power Part No. 11407). Heated coolant spray or steam can cause personal injury. Check the coolant level. Refer to Check Coolant Level in Section 5.
Add coolant if necessary. Place the AUTO/MANUAL rocker switch in the AUTO position. Return the fire protection system to operating status. Drawing No. 9777, Section 7, Rev. 02-07