Cummins — Cummins CFP83 Series Fire Pump Drive Engines Operation & Maintenance Manual

Page 7-74 Section 7 – Adjustment, Repair, and Replacement CFP83 Series Battery Isolator Removal/Installation (Cont) Drawing No. 9777, Section 7, Rev. 02-07 NOTE: Refer to Drawing 10423 Sheet 2 for schematic details. Measure voltages at the most convenient location. With the engine off, verify the following voltages at the battery isolator terminals to ground: Terminal 1 indicates battery voltage. Terminal 2 indicates the other battery voltage. Terminal E indicates no voltage. Start the engine. Refer to Normal Local Starting Procedure in Section 3. With the engine running, verify the following voltages at the battery isolator terminals to ground: Terminal 1 indicates battery voltage.