Cummins — Cummins CFP83 Series Fire Pump Drive Engines Operation & Maintenance Manual

Section 7– Adjustment, Repair, and Replacement Page 7-77 CFP83 Series Voltmeter Removal/Installation Drawing No. 9777, Section 7, 02-07 Prepare Place the fire protection system in a safe mode for engine service. Place the AUTO/MANUAL rocker switch in the MANUAL position. REMOVE BATTERY POWER BEFORE SERVICING ENGINE OR CONTROLS For safety reasons, both batteries must be disconnected before performing service on the Firepump Engine or on any of its controls. Before disconnecting the batteries, place the Firepump Controller in its appropriate service position in order to avoid a “Battery Failure” alarm. Wear safety glasses when disconnecting batteries!

Next, disconnect both batteries at their terminals. Remove NOTE: Refer to Drawing 10423 Sheet 1 in 12 14 10 16 Section 13 for electrical schematic details. 8 18 Open the local control panel. NOTE: Ensure that the wires are clearly tagged VOLTS for reconnection. Loosen the nuts on the stud and remove the wires. Remove the nuts on the mounting bracket and remove the voltmeter from the panel.