Cummins — Cummins CFP83 Series Fire Pump Drive Engines Operation & Maintenance Manual

Section 7– Adjustment, Repair, and Replacement Page 7-79 CFP83 Series Battery Testing Batteries can emit explosive gases. To avoid injury, always ventilate the compartment before servicing the batteries. To avoid arcing, remove the negative (-) battery cable first and attach the negative (-) battery cable last. WARNING Acid is extremely dangerous and can damage the machinery and can also cause serious burns. Always provide a strong tank of soda water as a neutralizing agent when servicing the batteries. Wear goggles and protective clothing to avoid serious burns. NOTE : This section is for conventional batteries only. Maintenance-free batteries may be supplied by the customer.

These are sealed and do not require the addition of water. Also, specific gravity cannot be checked. If the batteries are not supplied by Cummins Fire Power, follow the battery manufacturer’s recommendations for testing and servicing their batteries. WARNING Drawing No. 9777, Section 7, 02-07 Prepare Place the fire protection system in a safe mode for engine service. Place the AUTO/MANUAL rocker switch in the MANUAL position. REMOVE BATTERY POWER BEFORE SERVICING ENGINE OR CONTROLS For safety reasons, both batteries must be disconnected before performing service on the Firepump Engine or on any of its controls.

Before disconnecting the batteries, place the Firepump Controller in its appropriate service position in order to avoid a “Battery Failure” alarm. Wear safety glasses when disconnecting batteries! Next, disconnect both batteries at their terminals.