Page 7-80 Section 7 – Adjustment, Repair, and Replacement CFP83 Series Battery Testing (Cont) Check Electrolyte Level Remove all cell covers for both sets of batteries. Check the electrolyte level in each cell of each battery. NOTE : Cummins recommends the use of a self- leveling filler. If a syringe type filler is used, use care to prevent overflow or splashing of acid from the cell. CAUTION Do not overfill the cell. Fill only to the level indication. CAUTION If a syringe type filler is used, use care to prevent overflow or splashing of acid from the cell. As required, fill each battery cell with distilled water. Install all cell covers for both sets of batteries.
If water was added, recharge the battery prior to checking specific gravity. Drawing No. 9777, Section 7, Rev. 02-07