Cummins — Cummins CFP83 Series Fire Pump Drive Engines Operation & Maintenance Manual

Section 7– Adjustment, Repair, and Replacement Page 7-81 CFP83 Series Battery Testing (Cont) Check Specific Gravity NOTE : If water has been added to a dry cell, recharge the battery to mix the added water with the existing battery electrolyte. This will prevent incorrect readings. NOTE : The battery must be more than about ј charged before the hydrometer readings can be accurate. Accurate readings may require several hours of charging for a fully discharged battery. Use a hydrometer to measure the specific gravity of each cell.

State of Charge and Specific Gravity* * At 26.7 o C [80 o F] Check the battery fluid column in the refractometer to determine the state of charge of each battery cell. NOTE : Evaluate the state of charge in respect to the local requirements. A cold location will require a greater specific gravity than a hot climate for the necessary cranking amperes. If charge is low, charge the batteries. Refer to Battery and Electrical Installation in Section 3. Drawing No. 9777, Section 7, 02-07 % Charged Non-Tropical Tropical 100% 1.265 1.225 75% 1.225 1.185 50% 1.190 1.150 25% 1.155 1.115 0% 1.120 1.080