Section 7– Adjustment, Repair, and Replacement Page 7-89 CFP83 Series Starter Motor Assembly Removal/Installation REMOVE BATTERY POWER BEFORE SERVICING ENGINE OR CONTROLS For safety reasons, both batteries must be disconnected before performing service on the Firepump Engine or on any of its controls. Before disconnecting the batteries, place the Firepump Controller in its appropriate service position in order to avoid a “Battery Failure” alarm. Wear safety glasses when disconnecting batteries! Next, disconnect both batteries at their terminals. Remove Disconnect the ground (-) cable from the battery. Identify each electrical wire with a tag indicating location.
Remove the battery cable from the solenoid. Drawing No. 9777, Section 7, 02-07 Prepare Place the fire protection system in a safe mode for engine service. Place the AUTO/MANUAL rocker switch in the MANUAL position.