Cummins — Cummins CFP83 Series Fire Pump Drive Engines Operation & Maintenance Manual

Page 7-212 Section 7 – Adjustment, Repair, and Replacement CFP83 Series Tachometer Removal/Installation (Cont) Install the new tachometer in reverse order. Refer to instructions for Tachometer Calibration in this section. For safety reasons, both batteries must be re- connected before putting the engine and fire protection system controller back in service. Wear safety glasses when reconnecting batteries! Reconnect the batteries at their terminals after all service work has been completed. Place the AUTO/MANUAL rocker switch in the AUTO position. Return the fire protection system controller back to operating status. Drawing No. 9777, Section 7, Rev. 02-07