Page 12-10 Section 12 – Troubleshooting CFP83 Series Coolant Contamination (Cont) Drawing No. 9777, Section 12, Rev. 02-07 Coolant Heat Exchanger is leaking raw water into the coolant. Coolant volume increases and pressure is relieved when the unit is operating. Antifreeze concentration decreases. Drain and flush the cooling system. Refer to Drain and Flush Cooling System in Section 5. Remove Coolant Heat Exchanger. Refer to Coolant Heat Exchanger Removal/Installation in Section 7. Perform a pressure test of the raw water side of the heat exchanger. Refer to Coolant Heat Exchanger Removal/Installation in Section 7. If the heat exchanger leaks, it should be replaced.
Install a known good Coolant Heat Exchanger. Refer to Coolant Heat Exchanger Removal/Installation in Section 7. Check and adjust raw water pressure regulator setpoints. Refer to Raw Water Piping, Lineup, and Configuration in Section 3. Check and, if required, replace the Zinc Plug. Refer to Inspect Heat Exchanger Zinc Plug in Section 5. Refill with correct mixture of antifreeze and water. Refer to Drain and Flush Cooling System in Section 5. Coolant is inadvertently contaminated with unknown liquids. Drain and flush the cooling system. Refill with correct mixture of antifreeze and water. Refer to Drain and Flush Cooling System in Section 5. Contact an Authorized Cummins Repair Facility.