Page 12-12 Section 12 – Troubleshooting CFP83 Series Coolant Temperature Above Normal NOTE: The thermostat’s normal operating temperature range is 82-95 o C [180-203 o F]. The High Water Temperature lamp on the local control panel (see Instrument Panel in Section 2) illuminates at 93 (92-94) o C [200 (198-202) o F]. The lamp will only illuminate if the engine is running. If the lamp is illuminated or if temperature is otherwise excessive, the engine should be stopped as soon as practical and the problem corrected. Drawing No. 9777, Section 12, Rev. 02-07 Cause Correction Raw water flow is improperly aligned.
Check that the raw water manifold is aligned for normal flow through the solenoid valve (preferred) or bypass flow around the solenoid valve (alternative). (Refer to Drawing 9659 in Section 13.) Align flow if required. Raw water pressure regulator is improperly adjusted. NOTE: Pressure should be about 414 kPa [60 psig] or slightly less. Check the raw water pressure indication. If pressure is indicated but is low, adjust the regulator (Refer to Check Raw Water Pressure Regulator Setpoints in Section 3.) If pressure is not indicated or is excessively low, go to Raw water solenoid has failed in this table. Raw water solenoid has failed.
If pressure is excessively low when aligned for normal flow, open the bypass valves. Then, when practical, troubleshoot the raw water solenoid valve. Refer to Raw Water Solenoid Valve Fails to Operate in this section. If the solenoid valve operates, replace the pressure regulator. (Refer to Raw Water Pressure Regulator Removal/Installation in Section 7.) If pressure is excessively low when aligned for bypass flow, open the normal valves. Then, when practical, replace the pressure regulator. (Refer to Raw Water Pressure Regulator Removal/Installation in Section 7.)