Cummins — Cummins CFP83 Series Fire Pump Drive Engines Operation & Maintenance Manual

Section 12 – Troubleshooting Page 12-13 CFP83 Series Coolant Temperature Above Normal (Cont) Drawing No. 9777, Section 12, Rev. 02-07 Cause Correction Raw water piping or heat exchanger is plugged. Check the raw water strainer for blockage. Refer to Drawing 9659 in Section 13. Clean the strainer if necessary. Check the Cummins supplied raw water piping for blockage. Clean the piping if necessary. Check the customer supplied raw water piping for blockage. Remove any blockage. Check for flow through the heat exchanger. If necessary, replace the heat exchanger. Refer to Coolant Heat Exchanger Removal/Installation in Section 7. Coolant level is below specification. Check the coolant level.

Refer to Check Coolant Level in Section 5. Add coolant as required. If coolant level was excessively low, go to Excessive Coolant Loss in this section. Cooling system hose is collapsed or restricted. Inspect the hoses. Refer to Check Hose Condition in Section 5. Replace any damaged hoses. Refer to Coolant Hose Removal/Installation in Section 7. Coolant thermostat is malfunctioning. Remove and test the coolant thermostat. Refer to Coolant Thermostat Removal/Installation in Section 7. Replace the thermostat if it is defective. Coolant water pump is malfunctioning. Remove and inspect the water pump. Refer to Coolant Water Pump Removal/Installation in Section 7.

Replace the thermostat if it is defective.