Cummins — Cummins CFP83 Series Fire Pump Drive Engines Operation & Maintenance Manual

Section 12 – Troubleshooting Page 12-87 CFP83 Series Lubricating Oil Consumption Excessive (Cont) Drawing No. 9777, Section 12, Rev. 02-07 Cause Correction Piston rings not sealing (blue smoke). Check for excessive blowby. Refer to Engine Testing (Chassis Dynamometer) (014-002) in Troubleshooting and Repair Manual C Series Engines, Bulletin Number 3666003-02. Valve seals are worn. Inspect the valve seals. Replace the valve seals, if necessary. Refer to Valve Guide Seal, Cylinder Head (002-016) and Valve, Cylinder Head (002-020) in Troubleshooting and Repair Manual C Series Engines, Bulletin Number 3666003-02. Contact a Cummins Authorized Repair Facility.