Page 3-26 Section 3 – Installation and Operation CFP83 Series Initial Start-Up NOTE : Contact personnel responsible for the fire protection system before starting and to obtain approval to service or repair the system. Drawing No. 9777, Section 3, Rev. 02-07 Check the Raw Water Valves CAUTION The raw water lines to and from the fire pump must be open, and there must be sufficient water to the heat exchanger when the engine has started. Insufficient water supply will cause overheating, resulting in engine failure. Align raw water supply to the raw water supply valves. Align drainage from the heat exchanger raw water outlet. Open the raw water supply valves as shown.
Check the Engine Coolant Supply Close all cooling system drains. Verify that the vents are opened.