Page 3-42 Section 3 – Installation and Operation CFP83 Series Overspeed Setpoint Adjustment and Testing (Cont) Remove the calibrating screw cover from the electronic overspeed switch. NOTE : Turn the small screw on the potentiometer near the word “OVERSPEED” clockwise to increase trip speed. Turn it counter- clockwise to reduce trip speed. If the OVERSPEED light is illuminated with the signal present, perform the following steps: Reduce the signal frequency. Press the RESET button. Turn the potentiometer clockwise to raise the setpoint. Increase the signal frequency to setpoint. With the OVERSPEED light off, slowly turn the potentiometer counter-clockwise until the light is just illuminated.
NOTE : Repeat the adjustments as required to make the finest adjustment practical. When the setpoint is adjusted, perform the following steps: Replace the screw cover at the potentiometer. Disconnect the signal generator. Reset the light. Reconnect the speed sensor input. Perform the Test Procedure as outlined to check the effect of the adjustment. Drawing No. 9777, Section 3, Rev. 02-07