Cab Heater and Air Conditioner, Valeo 83.00 Refrigerant Service Operations Leak Testing Methods will increase the apparent brightness of the UV dye at leak sights. General Information 1.2 Move the UV lamp along the entire refrig- erant system, looking for signs of damage or corrosion on the fittings, hose-to-line crimps, switch ports, service ports with caps installed (dye inside the port is not an indication of a leak), brazed or welded areas, and around all connections. Check for evaporator leaks by illuminating the condensate drain tube or hole using the UV lamp. Refrigerant is nearly odorless. As a result, all of it may leak away and not be noticed until the system stops cooling.

All vehicle refrigerant systems lose some refrigerant. Higher loss rates signal a need to locate and repair the leaks. Leaks are most often found at the compressor hose connections and at the various fittings and joints in the system. If unapproved replacement hoses are installed, refrigerant can be lost through hose perme- ation. 1.3 Move the UV lamp along the refrigerant system following a continuous path, so that no potential leak sites are missed. If a leak is found, continue to check the re- mainder of the system since other leaks may be present. There are two leak testing methods to detect leaks in the refrigerant system:

UV (ultraviolet) dye leak de- tection and electronic leak detection. Daimler Trucks North America LLC recommends using the UV dye leak detection whenever possible, even though there are some limitations to using this method. A leak on the front seal of the compressor must be verified using a heated diode leak detector method described under the heading "Electronic Leak Detection" in this subject. Visible dye on the front of the compressor clutch does not verify that there is a repairable leak at the front seal. Evaporator leaks may not show up with dye, and must be checked using a heated diode leak detector if dye is not present at the condensate drain. UV Dye Leak Detection 2.

After repairing a leak, remove all UV dye residue remaining on the outside of the refrigerant sys- tem using the cleaner provided by the dye manu- facturer, or a comparable cleaner. Use a spray bottle of cleaner, a toothbrush, and a spray bottle of clean water for hard-to-reach areas. NOTE: Minor UV dye residue, or residue that is impossible to reach, will lose its fluorescence over time. 3. See Table 3 for a list of products that have been tested and approved for use by Freightliner deal- ers. WARNING 4. Close the hood and remove the chocks from the tires. Electronic Leak Detection IMPORTANT:

When using the UV dye leak detec- tion method, always wear protective eyewear that blocks UV rays and enhances the visibility of the dye. Always wear nonleather gloves and protec- tive eyewear when servicing the air conditioning system. Leather gloves do not adequately protect from freezing refrigerant. NOTE: Do not try to use a leak tester right after connecting or disconnecting service hoses. Traces of refrigerant at the fittings can falsely signal a leak. Always verify a leak by blowing shop air in to the area of the suspected leak and checking the area again. 1. Inspect the refrigerant system for leaks using a UV lamp.

1.1 Inspect the entire refrigerant system under low lighting using a UV lamp. Low lighting When checking for leaks, move the probe all the way around the fitting or suspected leak. Business Class M2 Workshop Manual, Supplement 20, September 2011 220/7