Freightliner — Freightliner Business Class M2 Workshop Manual

Cab Heater and Air Conditioner, Valeo 83.00 Refrigerant Service Operations Approved Products for UV Dye Leak Detection Type of Refrigerant Oil Product Description Vendor Part Number Freightliner Part Number Website Address Tracerline BigEZ Kit—Can be injected without discharging the system. Each kit includes one 4-oz (118-mL) cartridge and an injection tool. TP-9741CS ABP N83 327911 PAG www.tracerli- ne.com A 4-oz (118-mL) replacement car- tridge services 16 vehicles. TP-9760-0004CS ABP N83 327961 An 8-oz (237-mL) replacement car- tridge services 32 vehicles. TP-9760-0108 ABP N83 327951 Tracerline BigEZ Kit—Can be injected with- out discharging the system.

TP-9742CS ABP N83 327910 Each kit includes one 4-oz (118-mL) cartridge and an injection tool. POE/ universal www.tracerli- ne.com A 4-oz (118-mL) replacement car- tridge services 16 vehicles. TP-9770-0004CS ABP N83 327950 An 8-oz (237-mL) replacement car- tridge services 32 vehicles. TP-9770-108 ABP N83 327960 Tracerline Optimax UV Lamp TP-8680 ABP N83 327985 www.tracerli- ne.com Bright Solutions UV Lamp BSL760 ABP N83 327967 www.brightsol.com Service Valve Cap PH 660412 Table 3, Approved Products for UV Dye Leak Detection Daimler Trucks North America LLC recommends using only certain makes of the heated diode and infrared (IR) types of electronic leak detectors. 2.

Leak test with the engine turned off. 3. Charge the air conditioning system with sufficient refrigerant to indicate a gauge pressure of at least 50 psi (345 kPa) with the system not oper- ating. Typically, one-half pound (0.22 kg) of re- frigerant is sufficient to create 50 psi (345 kPa) of pressure. It may not be possible to produce this pressure and perform a valid leakage test, if the ambient temperature is less than 59°F (15°C). Recommended electronic heated diode type leak de- tectors are available from their manufacturers. See Table 4 . Another type of detector, the corona discharge type, is specifically not recommended .

Use the following procedures to locate refrigerant system refrigerant gas leaks using an electronic leak detector. 4. Be careful not to contaminate the detector probe tip if the part being tested is not clean. Wipe the part off with a dry shop towel or blow it off with shop air. Do not use cleaners or solvents, as many detectors are sensitive to their chemical ingredients. 1. Operate the electronic leak detector in accor- dance with the manufacturer’s instructions. Occa- sionally use a leak reference bottle of R-134a to ensure that the detector is working properly. Business Class M2 Workshop Manual, Supplement 20, September 2011 220/8