Cab Heater and Air Conditioner, Valeo 83.00 Troubleshooting System Diagnosis Using Refrigerant Pressure Readings Suction Pressure (low side) Discharge Pressure (high side) Possible Cause Remedy Improper belt tension. Check belt tension, repair as necessary. Restricted suction line. Remove the blockage or replace the component with the blockage as necessary. Determine cause of blockage and make further repairs as required. Normal Low Worn compressor. Replace compressor. Be sure to identify and correct cause of failure (e.g. system contamination, incorrect oil charge, leaks, etc.) Normal Normal No problem found. No action required.
Clean bugs, dirt, and any debris or obstructions blocking airflow through the condenser. Straighten condenser fins as necessary. Make sure engine fan is working properly and that fan shroud is in place. Restricted condenser airflow. Normal High Slight over-charge. Recover and evacuate the system, charge system with proper amount of pure R-134a refrigerant. Blockage in system. Remove the blockage or replace the component with the blockage as necessary. Determine cause of blockage and make further repairs as required. Low refrigerant charge. Thoroughly leak test the system using approved UV dye and/or electronic detector. Repair all leaks as necessary.
Charge system with proper amount of pure R-134a refrigerant. Low Low Frozen evaporator. Check refrigerant charge, check evaporator probe, correct as necessary. Faulty thermal expansion valve (TXV). Replace TXV. Faulty evaporator sensor. Replace sensor. Blockage downstream of the measurement point and before the expansion valve. Remove the blockage or replace the component with the blockage as necessary. Determine cause of blockage and make further repairs as required. Low Normal Low refrigerant charge. Thoroughly leak test the system using approved UV dye and/or electronic detector. Repair all leaks as necessary. Charge system with proper amount of pure R-134a refrigerant.
Faulty evaporator sensor. Replace sensor. Blockage downstream of the measurement point and before the expansion valve. Remove the blockage or replace the component with the blockage as necessary. Determine cause of blockage and make further repairs as required. Low High Low charge. Thoroughly leak test the system using approved UV dye and/or electronic detector. Repair all leaks as necessary. Charge system with proper amount of pure R-134a refrigerant. Faulty evaporator sensor. Replace sensor. Table 2, System Diagnosis Using Refrigerant Pressure Readings Business Class M2 Workshop Manual, Supplement 13, March 2008 300/3