Refrigerant Compressor, Sanden 83.01 Oil Check and Adding Oil to the Compressor WARNING Checking and Adding Refrigerant Oil Before doing any work, read the information in Safety Precautions 100 . Failure to read the safety precautions and to be aware of the dangers in- volved when working with refrigerant could lead to serious personal injury. WARNING Do not remove the oil fill plug on the refrigerant compressor without first recovering the system. Failure to recover the system could cause uncon- trolled release of high-pressure refrigerant, which can freeze skin and eye tissue causing serious injury or blindness.
General Information Compressors are charged with 10 floz (296 mL) of refrigerant oil. When the air conditioning system is operating, some refrigerant oil leaves the compressor and is circulated through the system with the refriger- ant, but the refrigerant oil cannot leave the system except when there is a leak, when the refrigerant is recovered, or when a system part is replaced. 1. Before beginning the refrigerant recovery pro- cess, make sure that the oil accumulator and oil drain bottle on the recovery/recycle machine are emptied of oil from previous repairs. 2. Recover all of the refrigerant from the system. See Section 83.00, Subject 220 for instructions.
It is important that the air conditioning system has the correct amount of refrigerant oil for proper opera- tion. Too little oil will result in compressor failure. Too much oil will degrade the performance of the air con- ditioner and may cause damage to the compressor. 3. Drain the recovered oil into the calibrated drain bottle of the recovery/recycle machine. Record the amount of oil recovered. IMPORTANT: Whenever the air conditioning system is discharged or recovered, the recov- ered oil, from the charging machine, must be measured in order to know how much oil must be returned to the system.
When a system com- ponent is replaced, a quantity of new oil equal to the recovered oil plus the oil coating the in- side of the component must be returned to the system. New oil must be from a container that has not been opened or that has been tightly sealed since its last use. 4. Inspect the refrigerant oil. If the oil has any of the following characteristics, flush and charge the system with 10 floz (296 mL) of oil. silver or black oil—indicates metal in the air conditioning system due to compressor wear milky oil—may indicate moisture in the sys- tem grit or debris in the oil 5. Properly dispose of the recovered oil. 6.
After repairs are finished, refer to Table 1 and use the following equation to determine the quantity of refrigerant oil that needs to be added to the system. Order Sanden PAG oil SKI 7803 1997 (type SP–20) for an 8.45-ounce (250-mL) can of refrigerant oil from your local Daimler parts distribution center. Tubing, funnels, or other equipment used to transfer the oil should be very clean and dry. [Quantity Recovered] + [Quantity for All Replaced Components] = [Quantity to add to the System] When handling refrigerant oil: Table 1 provides the quantities of oil that need to be added to the system for each component that was replaced.
Add the quantities listed in the table for each component that was replaced. Use the sum of the quantities or 6 floz (177 mL), whichever is less. Be sure that the oil is free of water, dust, metal powder, and other foreign substances; Do not mix the refrigerant oil with other types or viscosities of oil; Quickly seal the oil container after use. Refrig- erant oil absorbs moisture when exposed to the air for any period of time. Business Class M2 Workshop Manual, Supplement 13, March 2008 130/1