Deutz — 4.1 CONFIGURATION

SERDIA PARAMETERS 20-24 MK 3 TTG Parameter Unit Min. Max. typ Wert Description Page 7: Monitoring CoolTempMon.: ShutoffValue °C -30 130 118 Limit engine shutoff (130° = none) CoolTempMon.: Shutoff Delay s 0 600 0 Time delay engine shutoff CoolTempMon.: RecovValue °C -30 130 110,0 Reset limit CoolTempMon.: Fuel qty red. % 0 100 20 Fuel inj. quantity reduction (0% = none) CoolTempMon.: Red. delay s 0 600 15 Time delay fuel inj.quantity reduction CoolTempMon.: Alarm limit °C -30 130 113 Limit alarm OilPrMonitor: shutoff fact % 0 100 80 Factor for limit engine shutoff (0% = none) OilPrMonitor: shutoff delay % 0 100 20 Time delay engine shutoff OilPrMonitor:

recov fact % 0 100 20 Factor for reset value OilPrMon.: Power Red. delay s 0 600 15 Time delay fuel inj. quantity reduction Engine speed position valuesp 1/min 500...260 0 8 Engine speed values Oil pressure warning bar 0...0,5 Oil pressure warning limit=fct(speed) Page 9: Sensor calibration values The following values are dependent only on the type of sensor used and consequently do not generally need to be changed. BPSensor: upper err limit digits 0 1023 820 Boost pr. sensor: upper failure trigger point BPSensor: upper ref (2 bar) digits 0 1023 454 Boost pr. sensor: voltage at 2 bar BPSensor: lower ref (1 bar) digits 0 1023 219 Boost pr. sensor: voltage at 1 bar BPSensor:

lower err limit digits 0 1023 60 Boost.pr. sensor: lower failure trigger point OilPrSens.:upper err limit digits 1023 820 Oil pr. sensor: upper failure trigger point OilPrSens.:upper ref (5 bar) digits 0 1023 511 Oil pr. sensor: voltage at 5 bar OilPrSens.:lower ref (0 bar) digits 0 1023 102 Oil pr. sensor: voltage at 0 bar OilPrSens.:lower err limit digits 0 1023 40 Oil pr. sensor: lower failure trigger point CoolTempSens.:up. err limit digits 0 1023 1020 Coolant temp. sensor: upper failure trigger point CoolTempSens.:lo. err limit digits 0 1023 10 Coolant temp. sensor: lower failure trigger point LowerMapBranch TempSensor digits 0 26...394 4 values UpperMapBranch TempSensor.

digits 64...838 6 values Page 10: Setpoint gen. calibration values T1:setpoint sensor 0 255 2 Smoothing time constant SWG The following 8 parameters can be set with the menu ”Calibration”, see 4.3. - *SWG = setpoint sensor AccPedal(SWG1)up. err val. digits 0 65535 963 SWG1: upper failure trigger point AccPedal(SWG1)up. ref. digits 0 65535 922 SWG1: voltage max. position AccPedal(SWG1)lo. ref. digits 0 65535 103 SWG1: voltage min. position AccPedal(SWG1)lo. err val. digits 0 65535 62 SWG1: lower failure trigger point Hand thr. (SWG2)up. err val. digits 0 65535 961 SWG2: upper failure trigger point Hand thr. (SWG2)up. ref. digits 0 65535 830 SWG2: voltage max. position Hand thr. (SWG2)lo. ref.

digits 0 65535 190 SWG2: voltage min. position Hand thr. (SWG2)lo. err val. digits 0 65535 61 SWG2: lower failure trigger point