Heating and Air Conditioning TM1859 (14JUL04) 18-1830-17 700H Crawler Dozer 071404 PN=461 Evacuate R134a System SPECIFICATIONS Vacuum Pressure at Sea Level 98 kPa (980 mbar) (29 in. Hg) Vacuum Pressure Above Sea Subtract 3.4 kPa (34 mbar) (1 in. Level Hg) from 98 kPa (980 mbar) (29 in. Hg) for each 300 m (1000 ft) elevation ESSENTIAL TOOLS JT02045 R134a Refrigerant Recovery/Recycling and Charging Station a aJT02046 and JT02050 recovery and charging stations can be substituted for the JT02045 station. CAUTION: Do not remove high pressure relief valve (A). Air conditioning system will discharge rapidly causing possible injury. IMPORTANT:

Use correct refrigerant recovery, recycling and charging stations. DO –19–22FEB95 NOT mix refrigerant, hoses, fittings, components or refrigerant oils. T8422AC Do not run compressor while evacuating. 1. Connect refrigerant recovery, recycling and charging A—High Pressure Relief Valve station. (See R134a Refrigerant Recovery, Recycling B—High Pressure Test Port C—Red Hose and Charging Station Installation Procedure in this D—Blue Hose group.) E—High Pressure Hose F—Low Pressure Hose 2. Open low and high pressure valves on refrigerant G—Low Pressure Test Port recovery, recycling and charging station. H—Refrigerant Recovery/Recycling and Charging Station 3.

Follow the manufacturer’s instructions and evacuate the system. (See Evacuate R134a System in this group.) NOTE: The vacuum specifications listed are for sea level conditions. Subtract 3.4 kPa (34 mbar) (1 in. Hg) from 98 kPa (980 mbar) (29 in. Hg) for each 300 m (1000 ft) elevation above sea level. 4. Evacuate system until low pressure gauge registers 98 kPa (980 mbar) (29 in. Hg) vacuum. Continued on next page CED,OUTX547,178 –19–21OCT98–1/2 18 1830 17 SPECIFICATIONS Vacuum Pressure at Sea Level 98 kPa (980 mbar) (29 in. Hg) Vacuum Pressure Above Sea Level Subtract 3.4 kPa (34 mbar) (1 in. Hg) from 98 kPa (980 mbar) (29 in. Hg) for each 300 m (1000 ft) elevation