Heating and Air Conditioning If 98 kPa (980 mbar) (29 in. Hg) vacuum cannot be obtained in 15 minutes. Test the system for leaks. (See Leak Testing, 9031-25.) Correct any leaks. Specification Vacuum—Pressure at Sea Level 98 kPa (980 mbar) (29 in. Hg) .............. Pressure Above Sea Level Subtract 3.4 kPa (34 mbar) (1 in. Hg) from 98 kPa (980 mbar) (29 in. Hg) for each 300 m (1000 ft) elevation ................... 18 1830 18 5. When vacuum is 98 kPa (980 mbar) (29 in. Hg), close low-side and high-side valves. Turn vacuum pump off. 6. If the vacuum decreases more than 3.4 kPa (34 mbar) (1 in. Hg) in 5 minutes, there is a leak in the system. 7. Repair leak. (See Leak Testing, 9031-25). 8.
If the vacuum can be held without a 3.4 kPa (34 mbar) (1 in. Hg) decrease. Open low-side and high-side valves. 9. Evacuate system for 30 minutes after 98 kPa (980 mbar) (29 in. Hg) vacuum is reached. 10. Close low-side and high-side valves. Stop evacuation. 11. Charge the system. (See Charge R134a System procedure in this group.) CED,OUTX547,178 –19–21OCT98–2/2 TM1859 (14JUL04) 18-1830-18 700H Crawler Dozer 071404 PN=462