Purge Air Conditioner System Heating and Air Conditioning 3. Connect gauge manifold discharge hose to compressor discharge post, and open valve. Disconnect discharge hose from gauge manifold to allow purging nitrogen to atmosphere. 4. Open nitrogen tank valve and adjust regulator to Specification. Purge system for two minutes. Disconnect nitrogen supply. IMPORTANT: Air compressors used for purging systems require a water separator. Purging without a separator adds moisture, creating hydrofluoric acid when combined with refrigerant oil. Acid is corrosive to metal tubing. 18 1830 22 Specification Nitrogen Purge—Pressure 275 kPa (40 psi) (2.75 bar) for two minutes .................. 1.
Connect dry nitrogen hose to gauge manifold center hose. 2. Connect gauge manifold suction hose to compressor suction port, and open valves. 5. Evacuate the system. (See Evacuate R134a System in this group.) CED,TX03399,2292 –19–09DEC98–1/1 TM1859 (14JUL04) 18-1830-22 700H Crawler Dozer 071404 PN=466 SPECIFICATIONS Nitrogen Purge Pressure. 275 kPa (40 psi) (2.75 bar) for two minutes