Cummins — 4021531

Cooling System QSB4.5 and QSB6.7 Page 7-4 Section 7 - Maintenance Procedures at 2000 Hours or 2 Years Check for damaged hoses and loose or damaged hose clamps. Replace as required. Check the radiator for leaks, damage, and buildup of dirt. Clean and replace as required. Flush CAUTION The system must be filled properly to prevent air locks. During filling, air must be vented from the engine coolant passages. Wait 2 to 3 minutes to allow air to be vented; then add mixture to bring the level to the top. To be sure air is vented during the fill process: The thermostat has check balls that allow air to vent through the thermostat when the thermostat is closed.

A deaeration port is located next to the water outlet connection which connects to the top tank/coolant recovery tank of the cooling system. This provides adequate venting for a fill rate of 19 liters [5 gal.] per minute. NOTE: An alternate to using sodium carbonate, as outlined in this procedure, is to use RESTORE™. RESTORE™ is a heavy-duty cooling system cleaner that removes corrosion products, silica gel, and other deposits. The performance of RESTORE™ is dependent on time, temperature, and concentration levels.

An extremely scaled or flow-restricted system, for example, can require higher concentrations of cleaners, higher temperatures, or longer cleaning times or the use of RESTORE Plus™. Up to twice the recommended concentration levels of RESTORE™ can be used safely. RESTORE Plus™ must be used only at its recommended concentration level. Extremely scaled or fouled systems can require more than one cleaning.