5. ALARMS 5.3 LIST OF ALARMS DISPLAYED BY SERDIA SERDIA ALARM N° 84 DESCRIPTION The control unit detects that the power input to the turbo charge pressure sensor is non-existent or incorrect. CHECK Check that the power input to the turbo charge pressure sensor is correct (5 Vdc approx measured between pin 3 (pos- itive) and pin 1 (negative) of connector “B48”) . Turn the starter key first to “O” (OFF) and then back to the “I” (ON) position.

See if the alarm is still indicated; if so, contact Technical Assistance 20-158 0.012.8732.4 25 10 24 23 2 14 1 10 23 24 25 MX1 1 2 14 MX2 GND4 MS1 J1 10 2 3 24 25 1 0.013.5915.4 7 29 2 7 7 F30 7.5A +15 0441.9533 23 24 25 B48 1 2 3 2 0421.3172 p 3 24 2 5 2 3 2 D0022731 1 2 14