Deutz — 8.2 EMR1

SERDIA WHAT TO DO IF...? b) Series resistors in the supply lines. Manual throttle calibration: The two potentiometer end stops must be calibrated. The aim of calibration is to inform the control unit of the limit values for the two end stops: "Potentiometer stop LI speed" as the lower and "Potentiometer rated speed" as the upper reference point. Also, the "upper fault value" (+5 % from upper reference point) and "lower fault value" (-5 % from upper reference point) must be entered relative to the two reference points. Parameter designations 8.2.4 EXAMPLE OF FAULT FINDING Fault finding: Connection broken? not OK Restore the connection. OK Plug contacts dirty or corroded?

not OK Clean plug, replace if necessary. OK Sensor faulty? not OK Replace sensor. OK Cable harness faulty? not OK Check the harness, replace if necessary. 20-309 Configuration screen Calibration screen Value Hand thr.(SWG2)up. err val. Hand throttle(SWG2) upper fault limit(upper limit...5V) Rated engine speed x 1.05+ Hand thr.(SWG2)up. ref Hand throttle(SWG2) max.eng. speed (upper limit) Rated engine speed Hand thr.(SWG2)lo. ref Hand throttle(SWG2) min. eng.speed (lower limit) Low idling engine speed Hand thr.(SWG2)lo. err val. Hand throttle(SWG2) lower fault limit (0V...lower limit) LI engine speed - 0.05 x rated eng. speed