TESTING AND ADJUSTING STANDARD VALUE TABLE FOR ELECTRICAL PARTS Sys- tem Measurement conditions 1) Turn starting switch ON. 2) Turn fuel control dial to MAX position. 3) Turn pump prolix switch OFF. 1) Turn starting switch ON. 2) Turn fuel control dial to MAX position. 3) All levers at neutral. Control system 1) Turn starting switch ON. 2) Insert T-adapter. 1) Turn starting switch ON. 2) Insert T-adapter. 20-16 Name of component Connector No.
Inspec- tion method Judgement table Engine throttle, pump controller TVC solenoid valve (default value) C02 Measure current If the condition is as shown in the table below, it is normal • General operation mode Between (8) - (18) 650 ± 40mA LS-EPC solenoid valve (default value) C02 Measure current If the condition is as shown in the table below, it is normal • General operation mode Between (7) - (17) 800 ± 80mA L.H.
knob switch C03 Measure voltage If the condition is as shown in the table below, it is normal When switch is ON Between 20 - 28 V When switch is OFF (9) - GND 0 - 1 V S-NET C17 Measure voltage If the condition is as shown in the table below, it is normal (4), (12) - GND 4 - 8 V Between (8) - (18) 650 ± 40mA Between (7) - (17) 800 ± 80mA When switch is ON Between (9) - GND 20 - 28 V When switch is OFF 0 - 1 V (4), (12) - GND 4 - 8 V