78 Maintenance Section Battery Charger - Check i01039758 Battery Charger - Check The battery emits smoke or a dense vapor (gas). Perform one of the following procedures if the battery shows symptoms of overcharging: SMCS Code: 1401-535 Reduce the rate of charging by a significant amount. Complete the charging at the reduced rate. Checking Before Start-Up Check the battery charger for proper operation. If the batteries are properly charged, the needle of the ammeter will register near (zero). Turn OFF the charger. The battery charger must not produce excessive current during start-up. Alternatively, the charger must be automatically disconnected for start-up.

If the engine has an alternator, the charger must be automatically disconnected during start-up and during engine operation. Table 36 describes the effects of overcharging on different types of batteries. Table 36 Charging the Battery Never disconnect any charging unit circuit or bat- tery circuit cable from the battery when the charg- ing unit is operated. A spark can cause an explo- sion from the flammable vapor mixture of hydro- gen and oxygen that is released from the elec- trolyte through the battery outlets. Injury to per- sonnel can be the result. Perform the following procedure to charge the battery: 1. Ensure that the charger is turned OFF. 2.

Adjust the voltage of the charger in order to match the voltage of the battery. 3. Connect the POSITIVE lead of the charger to the POSITIVE battery terminal. Connect the NEGATIVE lead of the charger to the NEGATIVE battery terminal. Checking After Stopping Ensure that the battery charger is connected properly. Observe the meter of the charger. Record the amperage. 4. Turn ON the battery charger. Overcharging of Batteries i01539754 Belt - Inspect Overcharging reduces the service life of batteries. Use a battery charger that will not overcharge the battery. DO NOT charge the battery if the meter of the battery charger is in the RED zone. SMCS Code:

1357-040; 1357; 1397-040; 1397 Overcharging is indicated by the following symptoms: Inspection Belt tension should be checked initially between the first 20 to 40 hours of engine operation. The battery is very warm to the touch. A strong odor of acid is present. After the initial check, the belt tension should be checked at every oil change. Effects of Overcharging Batteries Type of Battery Effect Caterpillar General Service Batteries Caterpillar Premium High Output Batteries All of the battery cells have a low level of electrolyte. When the plates of the battery are inspected through the filler holes, the plates may appear to be warped. This is caused by an excessive temperature.

The battery may not pass a load test. Caterpillar Maintenance Free Batteries The battery may not accept a charging current. The battery may not pass a load test.