Komatsu — TROUBLESHOOTING EAGLE AIR CONDITIONER

TROUBLESHOOTING TROUBLE SHOOTING -EAGLE AIR CONDITIONER 20-269 WA250-3L (D) Problem - No display, the blower fan will not turn off, when the power is turned on. Possible Cause Inspection Remedy 1. Fan wires shorted to ground or vehicle chassis Disconnect the controller from the external harness, Individually check the continuity of the orange and black fan wires to ground, in the external harness. a) Unground and repair the shorted wiring. (E) Problem - Compressor clutch will not engage, unless defrost button is pushed. Possible Cause Inspection Remedy 1. Defective preset thermostat inside evaporator. Opened preset thermostat circuit. Broken thermostat wiring.

Evaporator coil temperature too cold for a/c operation. Push, hold defrost / temperature decrease buttons simultaneously. Check display for “OP” or “CL” readout. Disconnect red leads, and check for continuity across thermostat terminals. a) If “CL”, go to step 2. b) If “OP”, repair connections or wiring to preset thermostat. c) Replace preset thermostat. 2. Ambient cab temperature too cool (below 60E F). Set controller at 68-70E F, in a/c mode. Warm-up ambient temperature probe with fingers or heat gun. a) Verify if compressor clutch will pull in or not. b) If not go to step 3. 3. Opened ambient cab temperature probe (thermistor) Push, hold temp. Decrease/increase buttons simultaneously.

Display will read 40F if probe is defective. Disconnect the controller, check for continuity across black probe leads. Check resistance of thermistor. a) If display reads 49F, at room temperature, replace thermistor. b) Repair connections/wiring. c) If 10K ohms +/- 20%, thermistor is good. If 100K-1M ohms, replace thermistor.