Overview of NC Errors NC Errorcodes 15 Version: 1.1 Error(Hex) Error(Dec) Error type Description Index 0: first slave axis Index 1: second slave axis Index 2: etc. Value range: [0 ... 7] Unit: 1 4204 16900 Initialization Internal error An unexpected internal error has occurred. The following situations could be the cause:
Not enough TC router memory or Windows memory available to build the internal NC objects, internal NC structures and links (pointers between the NC objects) are faulty or missing, a fatal internal error has occurred in the calculation for a stop command, internal checks of the NC own logic and algorithms (self- monitoring software), unexpected modes and cases that are not regularly foreseen but are detected as erroneous. Often in such an error situation an additional error message is output in the logger (Windows Event Viewer), which can be helpful for more detailed analysis by Beckhoff or the user.
4205 16901 Parameter Cycle time for set execution task (SEC) not allowed The value of the cycle time for the NC set execution task (SEC 1/2) is not allowed, because it has passed outside the value range. Value range: [0.001 ... 0.1] Unit: s 4206 16902 Initialization "GROUPERR RANGE MAXELEMENTSINAXIS " _ _ 4207 16903 Parameter Cycle time for the set preparation task (SPP) not allowed The value of the cycle time for the NC set preparation task (SPP 1/2) is not allowed, because it has passed outside the value range. Value range: [0.001 ... 1.0] Unit: s 4208 16904 Parameter Single step mode not allowed The flag for the activation or deactivation of single step mode is not allowed. Value 0:
passive (buffer mode) Value 1: active (single step mode) Value range: [0, 1] Unit: 1 4209 16905 Parameter Group (de)activation invalid (internal error) The flag for (de)activating the full group is invalid. Value 0: group active Value 1: group passive Value range: [0, 1] Unit: 1 420A 16906 Initialization Set execution state (SEC state) not allowed (internal error) The value for the state of the set execution state machine (SEC state) is not allowed. This error occurs on passing outside the range of values, or if the state machine enters an error state. Value range: [0 ... 5] Unit: 1 420B 16907 Address Channel address