beckhoff TwinCAT 2 Motion — 2.4 Axis Errors

Overview of NC Errors NC Errorcodes 42 Version: 1.1 Error(Hex) Error(Dec) Error type Description 4356 17238 Monitoring Controller enable The controller enable for the axis is not available (see axis interface PlcToNc). This enable is required, for instance, for an axis positioning task. 4357 17239 Monitoring Feed enable minus A feed enable for movement in the negative direction is not available (see axis interface PlcToNc). This enable is required, for instance, for an axis positioning task in the negative direction. 4358 17240 Monitoring Feed enable plus A feed enable for movement in the positive direction is not present (see axis interface PlcToNc).

This enable is required, for instance, for an axis positioning task in the positive direction. 4359 17241 Monitoring Target velocity not allowed The target velocity requested for a positioning task is not allowed. This can happen if the velocity is less than or equal to zero, larger than the maximum permitted axis velocity, or, in the case of servo drives, is larger than the reference velocity of the axis (see axis and drive parameters). 435A 17242 Monitoring Movement smaller than one encoder increment (internal error) The movement required of an axis is, in relation to a positioning task, smaller than one encoder increment (see scaling factor).

This information is, however, handled internally in such a way that the positioning is considered to have been completed without an error message being returned. 435B 17243 Monitoring Set acceleration monitoring (internal error) The set acceleration has exceeded the maximum permitted acceleration or deceleration parameters of the axis. 435C 17244 Monitoring PEH time monitoring The PEH time monitoring has detected that, after the PEH monitoring time that follows a positioning has elapsed, the target position window has not been reached. The following points must be checked: Is the PEH monitoring time, in the sense of timeout monitoring, set to a sufficiently large value (e.g. 1-5 s)?

The PEH monitoring time must be chosen to be significantly larger than the target position monitoring time. Have the criteria for the target position monitoring (range window and time) been set too strictly? The PEH time monitoring only functions when target position monitoring is active! 435D 17245 Monitoring Motion Monitoring The actual position of the axis has not changed or has changed only slightly during the motion monitoring time. To avoid an error, the axis must change by more than the parameterized motion monitoring window in at least one NC cycle during the monitoring time. => Check, whether axis is mechanically blocked, or the encoder system failed.