beckhoff TwinCAT 2 Motion — 2.5 Encoder Errors

Overview of NC Errors NC Errorcodes 49 Version: 1.1 Error(Hex) Error(Dec) Error type Description 4425 17445 Parameter Filter mask for the raw value of the encoder not allowed The value for the filter mask of the encoder raw data in increments is invalid. Value range: [0x0, 0xFFFFFFFF] Unit: 1 4426 17446 Parameter Reference mask for the raw value of the encoder not allowed The value for the reference mask (increments per encoder turn, absolute resolution) for the raw data of the encoder is invalid. E.g. this value is used for axis reference sequence (calibration) with the reference mode "Software Sync". Value range: [0x0000000F, 0xFFFFFFFF] Unit:

1 4427 17447 Parameter Parameter "Dead time compensation mode" (encoder) is invalid The parameter for the dead time compensation mode on the NC encoder is invalid (OFF, ON with velocity, ON with velocity and acceleration). Value range: [0, 1, 2] Unit: 1 4428 17448 Parameter Parameter 'Control bits of the dead time compensation' (encoder) is invalid The parameter for the control bits of the dead time compensation at the encoder is invalid (e.g. relative or absolute time interpretation). Value range: [>0] Unit:

1 4429 17449 Parameter Parameter 'time shift of dead time compensation mode' (encoder) is invalid The parameter for the time shift of the dead time compensation (Time Shift in nanoseconds) at the encoder is invalid. Value range: [-1.0E9 .. 1.0E9] Unit: ns 4430 17456 Function Hardware latch activation (encoder) Activation of the encoder hardware latch was implicitly initiated by the referencing procedure. If this function has already been activated but a latch value has not yet become valid ("latch valid"), another call to the function is refused with this error.