Overview of NC Errors NC Errorcodes 51 Version: 1.1 Error(Hex) Error(Dec) Error type Description 4440 17472 Initialization Encoder initialization Encoder has not been initialized. Although the axis has been created, the rest of the initialization has not been performed: 1. Initialization of axis I/O, 2. Initialization of axis, 3. Reset axis. 4441 17473 Address Axis address The encoder does not have an axis, or the axis address has not been initialized. 4442 17474 Address Address I/O input structure Drive has no valid I/O input address in the process image. 4443 17475 Address Address I/O output structure The encoder does not have a valid I/O output address in the process image.
4450 17488 Monitoring Encoder counter underflow monitoring The encoder's incremental counter has underflowed. 4451 17489 Monitoring Encoder counter overflow monitoring The encoder's incremental counter has overflowed. 4460 17504 Monitoring Minimum software position limit (axis start) While monitoring for the minimum software position limit is active, an axis start has been performed on a position that is below the minimum software position limit. 4461 17505 Monitoring Maximum software position limit (axis start) While monitoring for the maximum software position limit is active, an axis start has been performed towards a position that is above the maximum software position limit.
4462 17506 Monitoring Minimum software position limit (positioning process) While monitoring for the minimum software position limit is active, the actual position has fallen below the minimum software position limit. For servo axes - they are continuously guided - this limit is extended by the amount of the parameterized lag error window.