beckhoff TwinCAT 2 Motion — 2.6 Controller Errors

Overview of NC Errors NC Errorcodes 57 Version: 1.1 Error(Hex) Error(Dec) Error type Description 4520 17696 Parameter Rate time Tv (controller) not allowed Velocity The value for the derivative action time is not allowed (D part of the PID T1 controller). Value range: [0.0, 60.0] Unit: s 4521 17697 Parameter Damping time Td (controller) not allowed Velocity The value for the damping time is not allowed (D part of the PID T1 controller). Suggested value: 0.1 * Tv Value range: [0.0.. 60.0] Unit: s 4522 17698 Parameter Limitation of the I part not allowed The parameter for limiting the I-part of a PI- or PID-controller is not allowed.

This internal state variable can be limited in percentage (1.0 corresponds to 100 percent). Value range: [0.0 .. 1.0] Unit: % 4523 17699 Parameter Limitation of the D part not allowed The parameter for limiting the D-part of a PI- or PID-controller is not allowed. This internal state variable can be limited in percentage (1.0 corresponds to 100 percent). Value range: [0.0 .. 1.0] Unit: % 4524 17700 Parameter Parameter 'Deactivation of the I part during travel' not allowed The boolean parameter for switching off the I-part during active positioning is invalid. Value range: [0, 1] Unit:

1 4525 17701 Parameter Parameter 'Filter time for P-T2 filter' not allowed The time T0 in seconds is not permissible as a filter time for the P-T2 element of the velocity controller. The filter time must be less than twice the NC SEC cycle time. Value range: [0.0, 60.0] Unit: s 4526 17702 Parameter Velocity observer: 'Parameterized mode' is not allowed The parameterized mode (0=OFF, 1=LUENBERGER) for the velocity observer of the special NC controller in the torque interface is not permitted. Value range: [0, 1] Unit: 1