Overview of NC Errors 2.8 Table Errors NC Errorcodes 66 Version: 1.1 Error(Hex) Error(Dec) Error type Description 4650 18000 Monitoring Drive hardware not ready to operate The drive hardware is not ready for operation. This can be caused by the following reasons: - the drive is in error state (hardware error) - the drive is in the start-up phase (e.g. after an axis reset preceded by a hardware error) - the drive lacks the controller enable (ENABLE) The time required for the "start-up" of a drive after a hardware error can be in the range of several seconds.
4651 18001 Monitoring Error in the cyclic communication of the drive (Life Counter) Reasons for this could be an interrupted fieldbus or a drive that is in the error state. 4652 18002 Monitoring Changing the table ID with active controller enable not allowed Changing (deselecting, selecting) the characteristic curve table ID is not permissible when the controller enable for the axis is active. 4655 18005 Monitoring Invalid I/O data for more than 'n' continuous NC cycles The axis (encoder or drive) has detected invalid I/O data for more than 'n' continuous NC cycles (NC SEC task) (e.g. n=3). As a consequence it is possible that the encoder referencing flag is reset to FALSE (i.e.
the encoder gets the state "unreferenced").EtherCAT fieldbus: "working counter error ('WCState')" Lightbus fieldbus: "CDL state error ('CdlState')" Error(Hex) Error(Dec) Error type Description 4A00 18944 Parameter Table ID not allowed The value for the table ID is not allowed, e.g. because it has already been assigned - is less than or equal to zero - or is greater than 255. Value range: [1 ... 255] Unit: 1 4A01 18945 Parameter Table type not permitted The value for the table type is not allowed as it is not defined. Value range: [1] Unit:
1 4A02 18946 Parameter Number of lines in the table not allowed The value of the number of lines in the table is not allowed, because, for example, it is smaller than two at linear interpolation and smaller than four at spline interpolation. Value range: [2, 0xFFFF] Unit: 1 4A03 18947 Parameter Number of columns in the table is not allowed The value of the number of columns in the table is not allowed, because, for example, it is less than or equal to zero (depends upon the type of table or slave). Value range: [1, 0xFFFF] Unit:
1 4A04 18948 Parameter Step size (position delta) not allowed The value for the step size between two lines (position delta) is not allowed, because, for example, it is less than or equal to zero. Value range: [0.001, 1.0E+6] Unit: e.g. mm