Simplicity on the Worksite Solutions Guide for FAQs: E5CC/E5EC Using ON/OFF Control The procedure to use ON/OFF control is given step by step in this section. The default setting is for reverse operation. Using ON/OFF Control For heating control, select reverse operation. For cooling control, select direct operation. Reverse Operation (Default) Direct Operation (Default) ON ON OFF Temperature Heating OFF Set point Set point Temperature Output turns ON if the temperature is lower than the set point. Output turns OFF if the temperature is greater than the set point. Output turns OFF if the temperature is lower than the set point.
Output turns ON if the temperature is greater than the set point. With ON/OFF control, you can adjust the reset width (called the hysteresis) for heating or cooling operation. The default setting is 1.0°C. Heating (Reverse) Operation Cooling (Direct) Operation When the output turns OFF at the set point, the temperature will decrease. You can set the temperature width that determines when the output will turn ON again. When the output turns OFF at the set point, the temperature will increase. You can set the temperature width that determines when the output will turn ON again. ON ON Heating OFF Temperature OFF Temperature Set point This width can be set as the hysteresis.
Simplicity on the Worksite Solutions Guide for FAQs: E5CC/E5EC 2-1 Step 1 Determining the Control Method 1 Select direct or reverse operation. Cooling 2 Adjust the hysteresis. Cooling Set point This width can be set as the hysteresis.