Mitsubishi — 3.8.9.1 State Graphic

Chapter 3 Creating and Editing Screens 3-146 Revision May, 2010 Property Description of Static Graphic Element Auto Change No When this option is selected, the value of the read address will be regarded as the state number. It means that the state number is determined by the value of the read address. For example, if the value of the read address $0 is 0, it will switch to 0th state; if the value of the read address $0 is 5, it will switch to 5th state. Yes When this option is selected and the value of the read address is a non-zero value, the static graphic element will change automatically.

For example, if the value of the read address $0 is 1 and higher (a non-zero value), the element will change the picture automatically according to the change time that the user set. When the value of the read address $0 is set to 0, the static graphic element will be back to the initial state and will not change the picture automatically. Variation When this option is selected, the property of the Read Address will be the condition of changing element picture. The element will change the picture automatically according to Read Address+1.

For example, if $0 is set to display the address of the element and $1 is set to change the element picture, when the value of the read address $1is 0, the user needs to use the read address $0 to switch the state of the static graphic element. At this time, the static graphic element will not change automatically, like when “No” option is selected. When $1 is 1 and higher (a non-zero value), the static graphic element will change the picture automatically, like when “Yes” option is selected.