drp024v240w1aa Datasheet
Related manuals
Document text
CliQ DIN Rail Power Supply 24V 240W 1Phase Features 3 Years warranty RoHS Compliant Over load protection Over voltage protection Over temperature protection Expected life time : 10 Years Power boost 150% for 3 seconds Compact design for easy handling Output terminals for fast wiring and easy installation With Conformal Coating (Class 1 Div 2 Hazard Loc) Model No. DRP 024V 240W 1AA Weight: 1.04KG Size: 121 mm X 85 mm X 118.5 mm (H x W x D) Redundancy : DRR-20A & DRR-40A or External ORing Diode Description The new CliQ DRP024V240W1AA is the latest offering from one of the World’s No.1 Power Supply Company.
The product offers a nominal output voltage of 24V, a wide temperature range from -20°C to 75°C and a minimum holdup time of >20ms@115Vac.The state-of-the-art design is made to withstand harsh industrial environments. The rugged, compact design aluminium case is shock and vibration resistant according to IEC60068-2-6. The 240 watts CliQ DIN Rail power supply provides over voltage, overload and thermal protection. Due to the wide input voltage range from 85 to 264Vac, the Delta’s CliQ power supply is worldwide usable, multiple output terminals for fast wiring and easy installation.
www.DeltaPSU.com 1 INPUT SPECIFICATION Input Voltage (Nominal) 100 - 240Vac Input Voltage range 85 - 264Vac Input Frequency (Nominal) 50 - 60Hz Input Frequency range 47 - 63Hz DC Input Voltage (Nominal) 125 - 250Vdc DC Input Voltage Range 120 - 375Vdc Input Current Efficiency > 85% @ 115Vac & 230Vac Inrush current (Cold Start) No damage & I2t rating at all I/P devices shall not exceed their rating Leakage Current Power Factor >0.96@115Vac & >0.90@230Vac OUTPUT SPECIFICATION Output Voltage (Nominal) 24 Vdc Output Voltage Tolerance +/- 2% (Initial set point tolerance) Output Voltage Adjust Range 22 – 28 Vdc Line Regulation Load Regulation Residual Ripple (PARD), 20MHz BW Output Current (Nominal) 10.0 A Power Derating above 50°C Derated Linearly 2.5% / °C Rise Time Start-Up Time Hold-Up Time > 20ms @ 115Vac & 230Vac (100% load, 25°C) Dynamic Response (Overshoot & +/-5% @ 0% - 100% load Undershoot O/P Voltage) Startup with capacitive loads 10,000µF @ nominal input & nominal O/P voltage 24V (25°C)
CliQ DIN Rail Power Supply 24V 240W 1Phase Device Description: 1) Output terminal block connector 2) Input terminal block connector 3) DC voltage adjustment potentiometer 4) DC OK control LED (green) 5) Universal mounting rail system Mechanical Drawing: www.DeltaPSU.com 2 MECHANICAL SPECIFICATION Dimension 121 mm X 85 mm X 118.5 mm (H x W x D) Weight 1.04kg Cooling System Convection Input Terminal Terminal Block with screw M4x3 pins (rated 300V/20A) Output Terminal Terminal Block with screw M4x2 pins / 2 pcs. (rated 300V/20A) Output Indicator Green LED (DC OK) Casing Aluminum
CliQ DIN Rail Power Supply 24V 240W 1Phase Block Diagram: www.DeltaPSU.com 3
CliQ DIN Rail Power Supply 24V 240W 1Phase Over Load Protection Over Voltage Protection The Power Supply is provided with an overload The Power Supply is protected by Over voltage in the protection (OLP/OCP) function which protects the power event that power supply feedback circuit fails the output supply from possible damage by over current. voltage will not be>32V +10%/-10%,under any Additionally power supply also has over temperature Line/Load and operating ambient conditions.
The unique protection (OTP) in case the over load condition persists for a longer duration and is below the overload trigger feature about this over voltage protection (OVP) is that power supply doesn’t shut down but goes in 2 nd level point but > 100% load. Typically the over load current regulation which is 30-32Vdc.
The Power supply will (I OL ) is > I SURGE (150%) output voltage will start drooping continue to deliver the power but due to high output down when the power supply reaches max power limit and will run into bouncing mode when the output reaches voltage it will be operating > 100% load (32V x 10A = 320Watts) if this condition persists the power supply will UVLO (under voltage point). The output voltage will sense OTP (Over Temperature Protection) and will go recover automatically when the overload condition is under bouncing mode. The power supply output voltage removed. will recover back to 24Vdc once the fault condition is Over Temperature Protection removed.
Additionally power supply also has over temperature Short Circuit Protection protection (OTP) as mentioned above this OTP comes The Power Supply also has a short circuit protection into picture when the over load condition persists for a which is in line with the overload protection and longer duration and the output current level is below the overload trigger point but > 100% load.Also in the event activates whenever there is a short across the output voltage, output goes in bouncing mode and remains of a higher ambient operating condition with 100% load until the fault is removed. the power supply will run into OTP when the Ambient temperature is > 80°C.
The protection is self recoverable when activated output voltage bounces until the operating ambient temperature of the power supply is reduced or the power supply is used within its power derating curve. www.DeltaPSU.com 4 PROTECTION 32V +10%/-10%, SELV output, Hicc-up Mode, Non-Latching Over Voltage Protection (Auto recovery). > 150% of rated load current, Hicc-up Mode, Non-Latching Over Load, Over Current Protection (Auto recovery). Over Temperature Protection recovery). Hicc-up Mode, Non-Latching, (Auto-recovery when the fault is Short Circuit Protection removed).