3. Instruction Set Operands: S : Alarm timer m : Time setting D : Alarm Explanations: 1. ANS instruction is used to drive the output alarm device in designated time. 2. Operand S valid range: T0~T183 Operand m valid range: K1~K32,767 (unit: 100 ms) Operand D valid range: S912~S1023 3. Flag: M1048 (ON: Alarm is active), M1049 (ON: Alarm monitoring is enabled) 4. See ANR instruction for more information If X3 = ON for more than 5 sec, alarm step relay S999 will be ON. S999 will remains ON after X3 is Program Example: reset.
(T10 will be reset, present value = 0) X3 3-111 API Mnemonic Operands Function Controllers SA2 ES2/EX2 SS2 SX2 SE Controllers 46 ANS Timed Annunciator Set ES2/EX2 SS2 SA2 SX2 SE Type OP Bit Devices Word devices Program Steps X Y M S K H KnX KnY KnM KnS T C D E F ANS: 7 steps S * m * D * PULSE 16-bit 32-bit ES2/EX2 SS2 SA2 SE SX2 ES2/EX2 SA2 ES2/EX2 SS2 SA2 SE SX2 SS2 SX2 SE ANS T10 K50 S999