Delta DVP-ES2 — 3.8 Detailed Instruction Explanation

DVP-ES2/EX2/SS2/SA2/SX2/SE&TP Operation Manual - Programming Explanations: 1. ANR instruction is used to reset an alarm. 2. When several alarm devices are ON, the alarm with smaller number will be reset. 3. This instruction is generally used in pulse execution mode (ANRP). Program Example: 1. If X20 and X21 are ON at the same time for more than 2 sec, the alarm S912 will be ON. If X20 or X21 is reset, alarm S912 will remain ON but T10 will be reset and present value is cleared. 2. If X20 and X21 are ON less than 2 sec, the present value of T10 will be cleared. 3. When X3 goes from OFF → ON, activated alarms S912 will be reset. 4.

When X3 goes from OFF → ON again, the alarm device with second lower number will be reset. X20 X21 X3 Points to note: Flags: 1. M1048 (indicating alarm status): When M1049 = ON, enabling any of the alarm S912~S1023 turns M1048 ON. 2. M1049 (Enabling alarm monitoring): When M1049 = ON, D1049 will automatically hold the lowest alarm number in active alarms. Application example of alarm device (production line):

X0 = Forward switch X1 = Backward switch X2 = Front position switch X3 = Back position switch X4 = Alarm reset button Y0 = Forward Y1 = Backward Y2 = Alarm indicator S912 = Forward alarm S920 = Backward alarm 3-112 API Mnemonic Function Controllers SA2 ES2/EX2 SS2 SX2 SE Controllers 47 ANR P Annunciator Reset SA2 ES2/EX2 SS2 SX2 SE OP Descriptions Program Steps N/A Instruction driven by contact is necessary. ANR, ANRP: 1 steps PULSE 16-bit 32-bit SA2 SA2 ES2/EX2 SS2 SA2 SE SX2 ES2/EX2 SS2 SX2 ES2/EX2 SS2 SX2 SE SE ANS T10 K20 S912 ANRP